Application: | Construction, Overhead, Power Station |
---|---|
Voltage: | Low and Medium Voltage Cable |
Current: | AC Cable |
Insulation Material: | XLPE |
Sheath Material: | N/A |
Material Shape: | Round Wire |
Samples: |
---|
Customization: |
---|
Suppliers with verified business licenses
Pos. | Description | Unit | Data |
1 | GENERAL DESIGN AND FEATURES | ||
1.1 | Rated Voltage U0/U (Um) | kV | 0.6/1 |
1.2 | Maximum Admissible current on air @ 40°C | A | 100 |
1.3 | Number of conductors (including neutral) | # | 7 |
1.4 | Cable schematic cross section | - | Please attach drawing |
1.5 | Cable weight | Kg/km | 418 |
1.6 | Minimum bending radius | mm | 401 |
1.7 | Minimum pullig force | N | 3000 |
1.8 | Maximum bundlediameter | mm | 22 |
1.9 | Maximum operating temperature (insulation) Normal operation/ Short Circuit (5s duration) | °C | 90/250 |
1.10 | Provision of Type test reports | Y/N | Please attach reports |
2 | CORES | ||
2.1 | Marking | - | Please attach description and layout (for Phases and Neutral) |
2.2 | Outer diameter | mm | 9.0 |
2.3 | Assembly of cores | ||
2.3.1 | Lay type ( helically) | Y/N | Y |
2.3.2 | Lay direction | - | right |
2.3.3 | Maximum length of lay | mm | 450 |
3 | PHASE CONDUCTOR | ||
3.1 | Material (detailed description) | - | Aluminum |
3.2 | Shape and compaction | - | Circular compact |
3.3 | Cross sectional area | mm2 | 25 |
3.4 | Class (IEC 60228) | # | 2 |
3.5 | Number of wires | # | 7 |
3.6 | Stranding lay direction | - | left |
3.7 | Conductor diameter | mm | 6.0 |
3.8 | Lay length (outer layer) | mm | 120 |
3.9 | Breaking force | DaN | 3000 |
3.10 | Conductor resistance | Ω/km | 1.20 |
4 | NEUTRAL CONDUCTOR (FILL IN JUST IF DIFFERENT FROM PHASE) | ||
4.1 | Material (detailed description) | - | Aluminium |
4.2 | Shape and compaction | - | Circular compact |
4.3 | Cross sectional area | mm2 | 25 |
4.4 | Class (IEC 60228) | 2 | |
4.5 | Number of wires | # | 7 |
4.6 | Stranding lay direction | - | left |
4.7 | Conductor diameter | mm | 6.0 |
4.8 | Lay length (outer layer) | mm | 120 |
4.9 | Breaking force | DaN | 3000 |
4.10 | Conductor resistance | Ω/km | 1.20 |
5 | INSULATION | ||
5.1 | Material (detailed description) | - | XLPE |
5.2 | Colour | - | BLACK |
5.3 | Thickness | ||
5.3.1 | Nominal value | mm | 1.4 |
5.3.2 | Mean value | mm | ≥1.4 |
5.3.3 | Minimum value | mm | ≥1.16 |
6 | DRUMS | ||
6.1 | Material | - | Iron wooden drum (1800*1120*1400) |
6.2 | Weight | kg | 210 |
6.3 | Cable length per drum | m | 4000 |
Q: How long does it take get my inquiry replied?
A: Mostly the inquiry will be replied within 12 hours. And the quote will be sent to you in 1-3 days. It depends on the technical parameters and requirements of the cable. We will give you a reasonable and accurate quote.
Q: Can I get samples before placing the order?
A: You will get a sample for free if we have the storage of that cable.
Q: What's the MOQ of your product?
A: The MOQ of our most product is 1000 meters. But if there's any exceptional situation, we can make some negotiations.
Fore More Information, Please do feel free to contact us!
Suppliers with verified business licenses